<HTML>
|
|
<HEAD>
|
|
<TITLE>M_DMM</TITLE>
|
|
<META NAME="Generator" CONTENT="KDOC ">
|
|
</HEAD>
|
|
<BODY bgcolor="#ffffff" text="#000000" link="#0000ff" vlink="#000099" alink= "#ffffff">
|
|
|
|
<table BORDER=0 COLS=1 WIDTH="100%" BGCOLOR="#FFFFCC" NOSAVE >
|
|
<tr ALIGN=CENTER VALIGN=CENTER NOSAVE>
|
|
<td NOSAVE><font face="Arial,Helvetica"><font size=+2></font></font>
|
|
<br><font face="Arial,Helvetica"><font size=+2>CCS Modul <b>M_DMM</b></font></font>
|
|
<br> </td>
|
|
</tr>
|
|
</table>
|
|
<PRE>
|
|
$Id: m_dmm.C,v 1.8 2006/01/09 16:04:14 gef1sa Exp $
|
|
---------------------------------------------------------------------
|
|
Kurzbeschreibung: Aufruf des Prozesses VXI_DMM
|
|
---------------------------------------------------------------------
|
|
Projekt: CCS
|
|
Sourcefile: m_dmm.C
|
|
Autor: RtW/TEF72-Juilfs (12.12.95)
|
|
Zielsystem: HP9000/V743 (HP-RT 2.0x), /Sxxx (HP-UX 9.0x)
|
|
Sprache: C++
|
|
---------------------------------------------------------------------
|
|
Prototyp:
|
|
MPI Schnittstelle
|
|
void m_dmm(shm_stringpointer *zeilen_info
|
|
,shm_stringpointer *zeilen_wert
|
|
,long index1
|
|
,long anzahl)
|
|
|
|
---------------------------------------------------------------------
|
|
Aufruf: im Vectorinterpreter
|
|
|
|
(*funktionen[modulnummer])
|
|
(Ssp_expand_zeile
|
|
,Ssp_expand_wert
|
|
,p_verwaltung->begin_modulblock
|
|
,p_verwaltung->anzahl_modulparameter);
|
|
|
|
|
|
|
|
|
|
---------------------------------------------------------------------
|
|
Funktionsbeschreibung:
|
|
Dieses Modul Ïbergibt seine Parameter an den Prozess VXI_DMM.
|
|
Im Prozess VXI_DMM werden dann die Messungen durchgefÏhrt.
|
|
Das MeÞergebnis wird per Returnparameter aus diesem Modul weiter
|
|
an das Modul M_AUSWERTEN gegeben. Die FunktionalitÌt des Multimeters
|
|
wird mit den Ûbergabeparametern eingestellt.
|
|
|
|
|
|
Beschreibung der ModulÏbergabeparameter:</pre><b><a name="param1">1</a> PRUEFSCHRITT</b><pre>
|
|
GAUDI PrÏfschritt
|
|
------------------------------</pre><b><a name="param2">2</a> POSITION</b><pre>
|
|
PAV- Position
|
|
------------------------------</pre><b><a name="param3">3</a> VXI_GERAET</b><pre> Name des GerÌtes laut PAM Beschreibungsfile
|
|
:DVM_01
|
|
:DVM_02
|
|
------------------------------</pre><b><a name="param4">4</a> DMM_FUNKTION</b><pre> MeÞfunktion
|
|
:DCV
|
|
:ACV
|
|
:RESISTANCE
|
|
------------------------------</pre><b><a name="param5">5</a> DMM_RANGE</b><pre>
|
|
Messbereich in Volt Kohm
|
|
0.0 Autorange (Sonderfunktion)
|
|
|
|
------------------------------</pre><b><a name="param6">6</a> DMM_APER_TIME</b><pre> Integrationszeit in s
|
|
Folgende Integrationszeiten können eingestellt werden.
|
|
10 us, 100us, 2,5 ms, 266, ms
|
|
sollte ein Integrationswerteingabe zwischen 2 Werten liegen, wird immer der nähere
|
|
verwendet.
|
|
|
|
|
|
|
|
------------------------------</pre><b><a name="param7">7</a> DMM_TRG_SOURCE</b><pre> Triggerart
|
|
:IMMEDIATE interner Trigger
|
|
:EXT externer Trigger
|
|
:HOLD Halten des MeÞergebnisses
|
|
------------------------------</pre><b><a name="param8">8</a> DMM_TRG_COUNT</b><pre> Anzahl der Triggerimpulse
|
|
------------------------------</pre><b><a name="param9">9</a> DMM_TRG_DELAY</b><pre> Delay zwischen 1. Trigger und 1.Messung
|
|
------------------------------</pre><b><a name="param10">10</a> DMM_SMP_SOURCE</b><pre> Quelle des Triggerimpulses
|
|
:IMMEDIATE Interner Trigger
|
|
:TIMER Keine Beschreibung
|
|
:SOFTWARE
|
|
:CONTROLREG
|
|
------------------------------</pre><b><a name="param11">11</a> DMM_SMP_COUNT</b><pre> Anzahl von Messungen per Trigger
|
|
-------------------------------</pre><b><a name="param12">12</a> DMM_SMP_PERIOD</b><pre> Zeitdauer zwischen 2 Messungen
|
|
-------------------------------</pre><b><a name="param13">13</a> DMM_AUTOZERO</b><pre> :ON
|
|
:OFF
|
|
:ONCE
|
|
-------------------------------</pre><b><a name="param14">14</a> DMM_OFFSET_COM</b><pre> :TRUE
|
|
:FALSE
|
|
-------------------------------</pre><b><a name="param15">15</a> DMM_INTERRUPT</b><pre> -------------------------------</pre><b><a name="param16">16</a> DMM_MASKE</b><pre> -------------------------------</pre><b><a name="param17">17</a> DMM_MODUS</b><pre> Steuerfunktion des DMM Einstellen Arm Lesen
|
|
INIT +
|
|
ARM +
|
|
READ +
|
|
S + +
|
|
AR (fÏr ACV) + +
|
|
M (= NORM) + + +
|
|
|
|
-------------------------------</pre><b><a name="param18">18</a> R_MESSWERT</b><pre> RÏckgabe des Messwertes
|
|
-------------------------------</pre><b><a name="param19">19</a> TIMEOUT</b><pre></pre><b><a name="param20">20</a> DIMENSION</b><pre></pre><b><a name="param21">21</a> MESSTEILERFAKTOR</b><pre>
|
|
|
|
|
|
|
|
######################################################################
|
|
Status:
|
|
Bisher wurden beim Aufruf von ACVINIT 2 Sekunden gewartet. Dies
|
|
soll mit einer neuen Prozessstruktur geändert werden. Die Funktion
|
|
RACV war dann relativ schnell <200 ms.
|
|
Die Prüfzeit erhöhte sich dadurch um 2 Sekunden
|
|
|
|
Änderung des Ablauf:
|
|
Ab der CCS Release 5.2 wird ist es möglich für das 2. DVM einen eigenen Prozess
|
|
aufzusetzen. Hiermit sollen die ACVINIT Aufrufe in den Backround Prozess
|
|
abgearbeitet werden.
|
|
|
|
|
|
|
|
Hieraus ergeben sich folgende Fälle.
|
|
1.) Es gibt nur einen Prozess VD
|
|
Bei Aufruf des ACVINIT wird der VI sofort wieder freigegeben und beim nächsten
|
|
Aufruf von M_DMM die restliche Initialisierunszeitzeit gewartet.
|
|
Dies bedeutet, dass ggf. beim nächsten DVM Aufruf DCV 2 Sekunden gewartet wird.
|
|
Grund: Die ACVINIT ist noch nicht abgeschlossen.
|
|
|
|
2.) Es gibt einen weiteren Prozess VD ---> V2
|
|
Bei Aufruf des ACVINIT wird der VI sofort wieder freigegeben und beim nächsten
|
|
Aufruf von M_DMM die restliche Initialisierunszeitzeit gewartet.
|
|
Da die DCV Messungen klassisch mit dem DVM_01 durchgeführt werden,
|
|
und das DVM_01 über dem Prozess VD gesteuert wird, gibt es keinen
|
|
Performance Verlust. Beim Aufsetzen des RACV wird eventuell die Initialisierung
|
|
Zeit des ACVINIT noch abgewartet.
|
|
Der Prüflisten Autor muß darauf achten das zwischen Aufruf ACVINIT und RACV
|
|
ca 2 Sekunden in der Prüfung verbraucht werden.
|
|
bei diesem Verfahren geht die InitialisierungsZeit nicht in die Prüfzeit ein,
|
|
da der Prozess V2 eigenständig das DVM_02 initialisiert, und vor der Initialisierung
|
|
den VI freigegeben hat.
|
|
Beim Umschalten des V2 Prozesses auf DCV Messungen muß natürlich wieder mit
|
|
einer uminitialisierungszeit von ca 300 ms gerechnet werden. Dies war aber
|
|
auch schon vorher der Fall.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
</PRE>
|
|
</BODY>
|
|
</HTML>
|